Triplex Service Drop Cable 3/0AWG Fulgar #3/0
Code Word: Fulgar
Size AWG (Phase Conductors): 3/0
Voltage: 600V
Number of cores: Triplex
Package : Export wooden drum & iron wooden drum or as customer require
Email: manager@hdcable.com.cn
|
Phase Conductor |
Strand or Compressed 1350-H19 Series Aluminum Conductor. |
|
Neutral(Messenger)Conductor |
Bare AAAC messenger. |
|
Insulation |
Black Cross Linked Polyethylene (XLP) Insulation. |
|
Rated voltage |
V |
600 |
|
Test voltage |
Veff kV/Hz |
4/50 |
|
Laying temperature |
°C |
min. -5 |
|
Operating temperature |
°C |
-30 ~ +90 |
|
Conductor temperature |
°C |
max. +90 |
|
Short-circuit temperature |
°C/s |
max. +250 /5 |
|
Bending radius (min.) |
mm |
20 × Ø of cable |
| Code Name | Fulgar |
| Phase Conductor Size/AWG | 3/0 |
| Phase Conductor Stranding | 19/w |
| Phase Conductor Insulation Thickness | 60 mls |
| Bare Neutral Messenger Size/AWG | 1/0 |
| Bare Neutral Messenger Stranding | 7 |
| Bare Neutral Messenger Breaking Strength | 4460 Lbs |
| Weight Per (lb/1000 ft) XLP | 543.4 Lbs |
| Weight (lb/1000 ft) Poly | 521.1 Lbs |
| Ampacity XLP | 275 Amps |
| Ampacity Poly | 215 Amps |