NFA2X Cable Application
Self-supporting overhead cable bundle, applied for electric power distribution in low voltage metropolitan, suburban and rural networks, for public lighting and house connections. Laid on pillars, consoles and house fronts.
NFA2X Cable Standard
HD 626 S1, VDE 0276-626
Abbreviation
N - Standard Cable type
F - Facade Cable
A - Aluminium conductor
2X - XLPE insulation
+N - with 'Messenger' Core
Round stranded Conductor for all sizes connection derived from the distribution system.
                    
                                        
                    
                        
                        
                            
                                
                                    Phase Conductor:
round Al conductor, multi wire stranded compacted (RM), class 2 acc. to HRN HD 383, phase conductors are marked with longitudinal protrusions (one, two or three)
Neutral (supporting) conductor:
Round AI conductor, multi wire stranded compacted (RM), class 2 acc. to HRN HD 383
Insulation:
XLPE (cross-linked polyethylene, recent mark: PE-X) compound TIX-2 or TIX-5 acc. to HD 626 S1
insulation colour:black                                
                             
                         
                     
                                        
                        
                        
                            
                                
                                    Temperature range: during installation: -5 °C
operating temperature: -30 °C up to +90 °C
at short circuit of max. 5 s: 250 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3.5 kV
Minimal inner bending radius: 12D                                
                             
                            
                         
                     
                                        
                    
                        
                        
                            
          
    
        
            | PHYSICAL   PROPERTIES | 
            ELECTRICAL   PROPERTIES | 
        
        
            Cable  
            Size | 
            Insulation  
            Thickness | 
            Approx. 
            Twisted  
            Diameter | 
            Approx.  
            Net.Weight | 
            Max. Conductor 
            Resistance  
            at 20 ℃ | 
            Current Carrying  
            Capacity  
            at 35℃ | 
            Calculated  
            Breaking  
            Force | 
        
        
            | mm2 | 
            mm | 
            mm | 
            Kg/km | 
            Ω/km | 
            A | 
            kg | 
        
        
            | 2x10rm | 
            1.2 | 
            14 | 
            94 | 
            3.08 | 
            54 | 
            322 | 
        
        
            | 2x16rm | 
            1.2 | 
            16 | 
            138 | 
            1.91 | 
            72 | 
            515 | 
        
        
            | 4x10rm | 
            1.2 | 
            17 | 
            187 | 
            3.08 | 
            54 | 
            644 | 
        
        
            | 4x16rm | 
            1.2 | 
            19 | 
            272 | 
            1.91 | 
            72 | 
            1030 | 
        
        
            | 4x25rm | 
            1.4 | 
            24 | 
            423 | 
            1.2 | 
            102 | 
            1610 | 
        
        
            | 4x35rm | 
            1.6 | 
            27 | 
            564 | 
            0.868 | 
            125 | 
            2250 |