556.5 MCM Dahlia AAC All Aluminum Stranded Conductor

All Aluminum Conductor 556.5 MCM Dahlia

Code Word: Dahlia

Number of Stranded: 19

Conductor Material: All Aluminum Conductor

Standard: ASTM B231

Email: manager@hdcable.com.cn

AAC Dahlia Conductor Application

556.5 MCM Dahlia AAC Cable can be used in low and medium voltage overhead lines. It’s commonly used in urban areas because of its ability to carry significant voltages over short distances. The long-lasting, corrosion resistant qualities of aluminum make this conductor a popular choice for use in coastal areas as well as for use in the railway and subway industries. Shipyards and offshore construction sites benefit from the conductor’s durability.556.5 MCM Dahlia AAC Cable can be used for most overhead transmission duties when conductor strength is not a factor. The conductor can also be used for primary and secondary distribution applications.

AAC (all aluminum conductor) is the most economical bare overhead conductor due to its lighter weight. It offers easier handling during installation and use of simpler fittings. The wire is corrosion resistant due to its homogeneous construction.
STANDARD :

AAC Dahlia Conductor Standard

-ASTM B-230: Aluminum 1350-H19 wire for electrical purposes.
- ASTM B 231: Concentric Lay Stranded Aluminum 1350 Conductors.
CONSTRUCTION :

AAC Dahlia Conductor Construction

Aluminum alloy 1350 wires concentric lay stranded wrapped helically around a central wire. Each successive layer has six wires more than the previous underlying layer. Outer layer is right hand lay and reversed in successive layers.

AAC Oxlip Conductor
PARAMETER :
Code name: Dahlia
Size AWG: 556.5
Stranding: 19
Stranding Class: AA
Diameter Individual Wire Aluminum (Inches): 0.1711
Diameter Complete Cable (O.D.) (Inches): 0.856
Cross Sectional Area (Sq. Inches): 0.4371
Weight Per 1000ft Total (Lbs.): 522.4
Rated Breaking Strength (Lbs.): 9750
Resistance DC 20°C Per 1000ft (Ω): 0.0311
Resistance DC 75°C Per 1000ft (Ω): 0.0382
Allowable Ampacity 90C (Amps): 703