Copper Airdac SEN Cable

Copper Airdac SEN Cable

Type of cable: Copper Airdac SEN Cable

Phase Conductor: Copper

Insulation : XLPE

Neutral Conductor: Copper Wire

Sheath: PE (Polyethylene)

Email: manager@hdcable.com.cn

Airdac SEN Cable Application


For use in electricity supply to houses, 600V. Strung in air from pole top distribution box to houses pre-paid electricity meter / main circuit breaker.

Airdac SEN Cable Standard

SANS 1507-6 
CONSTRUCTION :
Circular stranded hard drawn copper phase conductor, XLPE insulated with concentrically arranged identified neutral and bare earth conductors. Polyethylene sheathed 600/1000V service connection cable. Nylon ripcord laid under sheath. Manufactured to SANS 1507 -6.


 

Conductor: Stranded Copper Conductor
Insulation: Red XLPE
Neutral Conductor:PE insulated Solid Copper Wire
Neutral Insulation: XLPE
Ripcord: Nylon
Binder Tape:Polyester Tape
Pilot Core: PE Insulated Copper Wire
Earth Conductor: 3 bare Solid Copper Wire
Outer Sheath: Black PE (Polyethylene)
CHARACTERISTICS :
• Small overall diameter - concentric construction (SNE - Seperate Neutral Earth).
• Lower mass - due to smaller diameter - no steel wire armour.
• Increased safety - reliable earthing.
• Improved reliability - UV stable sheath and core insulation and water blocked.
• Tamper and vandal proof - unauthorised access to phase conductor inhibited by concentric layer.
• Easy strip with nylon ripcord. 
PARAMETER :

SEN Cable Parameter

Cable Size (mm²)
10 16
Phase Conductor (No. x OD)(mm)
7x1.35 7x1.68
Nominal InsulationThickness (mm)
1.0 1.0
Neutral Conductor (No. x OD)(mm)
7x1.33 7x1.76
Earth Conductor (No. x OD)(mm)
3x1.78 3x2.20
Nominal SheathThickness (mm)
1.6 1.6
Approximate Cable OD (mm)
12.8 14.5
Approximate Cable Mass (kg/km)
320 480
 