Three Core 12/20KV (Um=24KV) Unarmored Cable
Voltage: 12/20kV
Conductor: Copper or Aluminum
Operating Temperature: up to 90°C
Short Circuit Temperature: 250°C
Bending Radius: 15 x OD
Email: manager@hdcable.com.cn
XLPE(Cross linked polyethylene) insulated cable functions well for electricity transmission and distribution lines for its excellent electrical and physical properties, including the advantage of simplicity in construction, lightness in weight; convenience in application besides its excellent electrical, thermal, mechanical and anti-chemical corrosion properties.
GB/12706-2008, IEC60502,IEC 60228,IEC60332 BS 5467,BS 6622 , IS 1554 , IS 7098and ICEA S-66-524 etc.

Conductor: Plain annealed stranded compacted circular copper or aluminium conductor to IEC60228 class 2
Conductor Screen: Extruded semi-conductive compound
Insulation: XLPE (cross-linked polyethylene) rated at 90°C
Insulation Screen: Extruded semi-conductive compound
Metallic Screen: copper tape or a concentric layer of copper wires
Color for core identification: Red, Yellow ,Blue tape shall be applied between insulation screen and metallic screen ( The above identifying can be changed as user requirement)
Assembly : Three screened cores are laid up together ,if necessary filled with non-hygroscopic material compatible with insulation and covered with a layer of PVC sheath
Outer Sheath: PVC type ST2 to IEC 60502 or PE ,LSZH
| Specification | Outer diameter | Nominal thickness of insulation | Nominal sheath thickness | Approx. Outer diameter of cable | Approx. Weight of cable | Ampacity of cable | ||||
| Air | Soil | |||||||||
| CU | AL | Cu | Al | Cu | Al | |||||
| mm2 | mm | mm | mm | mm | kg/km | kg/km | A | A | A | A | 
| 3×25 | 6.0 | 5.5 | 2.6 | 49.9 | 2491.3 | 2025.0 | 125 | 96 | 135 | 105 | 
| 3×35 | 7.0 | 5.5 | 2.7 | 52.3 | 2922.3 | 2269.4 | 150 | 115 | 160 | 125 | 
| 3×50 | 8.4 | 5.5 | 2.8 | 55.5 | 3536.9 | 2604.2 | 175 | 135 | 190 | 150 | 
| 3×70 | 10.0 | 5.5 | 2.9 | 59.1 | 4314.1 | 3008.3 | 220 | 170 | 235 | 185 | 
| 3×95 | 11.5 | 5.5 | 3.0 | 62.6 | 5243.6 | 3471.5 | 265 | 205 | 285 | 220 | 
| 3×120 | 13.0 | 5.5 | 3.1 | 66.1 | 6142.2 | 3903.7 | 305 | 235 | 320 | 250 | 
| 3×150 | 14.5 | 5.5 | 3.2 | 69.5 | 7211.1 | 4413.0 | 350 | 270 | 365 | 285 | 
| 3×185 | 16.2 | 5.5 | 3.3 | 73.4 | 8423.3 | 4972.4 | 395 | 310 | 410 | 320 | 
| 3×240 | 18.4 | 5.5 | 3.5 | 78.5 | 10279.2 | 5802.3 | 465 | 365 | 475 | 370 | 
| 3×300 | 20.5 | 5.5 | 3.6 | 83.3 | 12247.7 | 6651.5 | 530 | 415 | 535 | 420 | 
| 3×400 | 23.5 | 5.5 | 3.9 | 90.2 | 15418.2 | 7956.7 | 615 | 485 | 605 | 480 | 
| Nominal section area (mm2) | Copper conductor(Ω/km) | Aluminum conductor(Ω/km) | 
| 1.5 | 12.1 | - | 
| 2.5 | 7.41 | 12.1 | 
| 4 | 4.61 | 7.41 | 
| 6 | 3.08 | 4.61 | 
| 10 | 1.83 | 3.08 | 
| 16 | 1.15 | 1.91 | 
| 25 | 0.727 | 1.20 | 
| 35 | 0.524 | 0.868 | 
| 50 | 0.387 | 0.641 | 
| 70 | 0.268 | 0.443 | 
| 95 | 0.193 | 0.320 | 
| 120 | 0.153 | 0.253 | 
| 150 | 0.124 | 0.206 | 
| 185 | 0.0991 | 0.164 | 
| 240 | 0.0754 | 0.125 | 
| 300 | 0.0601 | 0.100 | 
| 400 | 0.0470 | 0.0778 | 
| 500 | 0.0366 | 0.0605 | 
| 630 | 0.0283 | 0.0469 | 
Max. Permissible short-circuit current for conductor (reference value)
| Nominal section area (mm2) | Maximum permissible short-circuit current for conductor(1s)(KA) | |
| Copper conductor | Aluminum conductor | |
| 1.5 | 0.12 | 0.13 | 
| 2.5 | 0.32 | 0.22 | 
| 4 | 0.50 | 0.34 | 
| 6 | 0.76 | 0.51 | 
| 10 | 1.51 | 0.99 | 
| 16 | 2.39 | 1.56 | 
| 25 | 3.69 | 2.42 | 
| 35 | 5.15 | 3.37 | 
| 50 | 7.31 | 4.79 | 
| 70 | 10.2 | 6.68 | 
| 95 | 13.8 | 9.03 | 
| 120 | 17.4 | 11.4 | 
| 150 | 21.7 | 14.2 | 
| 185 | 26.7 | 17.5 | 
| 240 | 34.6 | 22.6 | 
| 300 | 43.1 | 28.2 | 
| 400 | 57.4 | 37.65 | 
| 500 | 71.7 | 47.0 | 
| 630 | 88.8 | 58.0 |